KVT-400 Troubleshooting Guide

Troubleshooting for the AutoVent KVT-400 wind-direction curtain controller.

KVT-400
Wind-direction curtains
DC curtain motors
Touch screen

Labeled KVT-400 controller board diagram showing the wind sensor terminals 96 to 99, temperature probes 1 and 2, the white and brown Xnet terminals, the 24 vdc power wires, rain sensor, 0-10v output, and Sensor #3 and #4 inputs

The screen only shows the AutoVent logo with a black background briefly, then goes black. Several seconds later it does it again.

The wind sensor gets power from the controller / screen board. If the wind sensor shorts out, the controller and screen will restart.

Test 1

Take a picture so you know how to reconnect the wires.

  • Disconnect terminal 96.
  • Disconnect the rain sensor’s 3rd terminal, labeled blue.
KVT-400 controller board with the wind sensor terminals circled in red at top and the Rain Sensor #1 terminals circled in red on the lower terminal row
Test 1: disconnect terminal 96 (top) and the rain sensor’s blue terminal (lower row).

Does the controller still reboot?

Stopped rebooting – go to Test 2.
Still reboots – disconnect all terminals 96, 97, 98 & 99 and all 4 rain sensor terminals.

If it still reboots, check power supply voltage. It should be 24 vdc between terminals 30 & 31, and 3.3 v between 96 & 97.

Test 2: testing wind sensor wires

This test assumes the controller stopped rebooting when all the weather sensor wires were disconnected in Test 1.

Go up to the weather sensor junction box:

  • Take a picture of the wires inside the junction box.
  • Disconnect all of the 8 wires coming up from the controller.
  • Make sure none of the now-loose wires are touching each other.
  • Reconnect all the wires down at the controller.
Interior of the weather sensor junction box with the terminal strip circled in red and the wind sensor cable entering through the bottom
Test 2: open the weather sensor junction box and disconnect the 8 wires coming up from the controller.

Does the controller reboot with only the wire connected?

No – replace the wind sensor. Or disconnect wind and then rain sensor to confirm the issue is with the wind sensor (most likely).
Yes – replace the wire.

Expansion box: 6th relay from the right on forever

The 6th relay stays on regardless of the output status.

  • Remove the 2nd top-left screw.

If the relay turns off as the screw is loosened, leave the fastener out permanently.

Expansion box showing the blue three-digit display board on the left and the green relay board on the right, with a pointer line indicating one of the plug-in relays
The expansion box display board and relay board.

Troubleshooting KVT-400 DC motor power

Check between blue & purple with a DC meter. With a motor running it should be about 24 v. Not running, it may read as high as 48 vdc.

Is 24 vac coming out of the transformer on the fat red wires?

Yes – the transformer is good. Go to the next step.
No – go to the transformer check. Check if 120 v is going into the transformer between white and yellow.

Is 24 vac going into the rectifier?

No – jump the solid state; does power go through?

Fans turn off whenever a curtain motor starts

The user tried to use the motor (blue & purple wires) on the KVT-400 to power a fan contactor. Bad idea, since the solid state is constantly turning the power off and on whenever a motor runs. His fan constantly cycled.

The user needs to power the fan contactors from a different power supply.

Curtain only goes open, doesn’t close (new KVT-400)

From the main screen, press the offending curtain, then press the little close button to the left of off.

If the curtain is wired correctly, the curtain will then close regardless, even if it’s at zero percent.

In this case, an inexperienced electrician was installing and wasn’t sure if the wires were connected correctly.

  • It was a loose screw on the aluminum busbar.

Curtain losing position

This was a 400 ft long curtain with a ShadyLane motor. It was taking 12 amps or 18 amps depending on its mood. We had to set the amp setpoint very high and use a bigger circuit breaker. Eventually the motor got replaced and the amps were more consistent.

Wind direction but no wind speed

Use the Test program in the About screen. Scroll to the wind meter test. Jump 98 & 99 at the control to make sure the input works at the controller. Then test again, jumping 98 & 99 up at the wind sensor junction box. If the controller correctly detects the jumper in both locations, replace the wind sensor.

Variable-speed fans not running after a storm

Check the 0-10 dc voltage between 5 & 6 as circled below. Put the black tester lead on – and the red tester lead on +.

Disconnect the wires from 5 & 6.

KVT-400 controller board with the 0-10v output terminals 5 and 6 circled in red on the lower terminal row, below the temperature sensor and Xnet labels
Check the 0-10 v output across terminals 5 & 6 (circled).

It should be exactly as shown on the variable speed button value. 100% means 10 v, 50% is 5 vdc.

KVT-400 touch screen reading 64.7 degrees, 0.0 MPH NW, No Rain, 0 amps, 0 percent RH, with the variable speed value of 56 percent circled in red and five curtain buttons showing open positions
The variable speed button value (56% circled) sets the expected 0-10 v reading.

If the voltage goes to nothing as soon as the VFD is connected back to 5 & 6, then a VFD is shorted out somewhere. Disconnect the VFDs one at a time until you find the offending VFD or shorted wire that needs to be replaced.

Display not on

  1. Disconnect the red wire from the power input.
  2. Measure DC voltage between the black & red wires.
    • Under 20 vdc – check the power input, or change the power supply.
    • If you get 24 vdc, then the power supply is good and something is shorting out the power supply.
  3. The short could be from the components that use 24 vdc.
KVT-400 controller board with the 24v power input terminals circled in red at the top right corner of the board
The 24 v power input terminals on the controller board.

Check the 24 vdc components in their most likely sequence:

  1. AV430 display board (disconnect the expansion box to check, but make sure power is off to disconnect / reconnect).
  2. AV5 in the expansion box.
  3. Rain sensor.
  4. Humidity sensor.
KVT-400 enclosure interior showing the DIN-rail power supply module at the bottom with red, white, blue and yellow wiring and the white sensor mounted on the back wall
The power supply inside the KVT-400 enclosure.

Replacing the LCD

Make sure power is off.

  1. Remove the 4 stainless screws (likely you can leave the wires attached).
  2. Lift the board off.
  3. Remove the 4 spacers. Use pliers to keep the spacers from spinning. Gently take them off, as their front screw heads are underneath the label (and we don’t want to ruin the label).
  4. Gently lift the AV430 out.
  5. Put the new AV430 in. Be careful not to stress the screen’s yellow ribbon cable. Slide it in over the screws without ramming, or the front label will get poked out.
  6. Put everything back together in reverse order.
KVT-400 controller board with the four mounting screws circled in red, one at each corner of the board
Remove the 4 stainless screws (circled) to lift the board off.

Power back up. Test the system. From the display, cycle all the relays to make sure they all work.

Set up the unit. All the parameters will have been lost, as they are stored in the AV430.

  • You will need to enter the number of curtains and fans and their starting relays.
  • You will need to set the direction of each curtain.
  • You will need to reteach all the curtains.

Expansion not communicating

Do the blue expansion boards only read zero on their screens?

The screens show how many times per second they are hearing from the main box. Zero is a bad deal – that means it is not talking. A functioning system should read 3.8 v DC between the white & brown.

Blue expansion board with its three-digit display circled in red, next to the green relay board with six plug-in relays and output terminals
The expansion board display shows how many times per second it hears from the main box; zero means it is not communicating.

Method to check communication (process of elimination)

  • Disconnect the brown & white wires (turn power off first).
  • Turn power back on. With a DC voltmeter, between the brown & white terminals it should read approx. 3.8 v. A zero volt reading means it is disconnected or the screen board is bad.
KVT-400 controller board with an arrow and red oval pointing to the white and brown Xnet terminals next to the 24v power terminals
The brown & white Xnet terminals should read approximately 3.8 v DC.

If it has 3.8 v when there is no expansion, but the voltage drops near zero when the expansion is connected, the blue expansion might need to be replaced.