Hoover Crowdgate Controller – User Guide
Setup and operation for the AutoVent Hoover Crowdgate controller (2020, v102).
VFD motor control
Up/Down & For/Rev motors
Wifi remote diagnostics

Overview
The Hoover Crowdgate controller runs a dairy crowd gate. It uses a custom VFD (variable frequency drive) and a small control board to drive two motors: an up/down motor that raises and lowers the gate, and a forward/reverse motor that drives the gate forward and back. Pushbuttons at the front and rear of the holding area, plus limit switches, tell the controller what to do, and control buttons and LEDs on the board make installation, testing, and troubleshooting easier.
Power in is 240v 20 amp single phase. The controller also has a wifi radio and setup screen, and supports Farmshield.net remote diagnostics. All gate control logic is done with a custom firmware loaded at the time of manufacture.
Features
- Adjustable torque: how hard the gate motor pushes is adjustable. This torque adjustment lets you set the max torque the gate uses. Note: cold weather takes more torque.
- Jog forward feature: press and release the Forward button to jog the gate forward for an adjustable amount of seconds. Each additional quick press and release of the Forward button adds additional time.
- Reversing feature: press Reverse and UP at the same time to make the gate go Up, then Back.
- Down jog feature: press and release Down quickly to jog the gate down.
- Control buttons to simplify installation and testing.
- LEDs to simplify troubleshooting.
- Easy-to-wire terminals to connect to button boxes and limit switches.
- Wifi setup screen and wifi radio.
- Keypad to change settings.
- Power in 240v 20 amp single phase.
Inside the controller
Inside the enclosure, the pushbutton control wires connect at one terminal block and the limit switches connect at another. Use normally open limit switches. The motor connects to the 3 pole relay, and the motor ground wire connects to the plate. If the motor goes the wrong way, swap 2 of the conductors.
- The 5v power supply is for the wifi.
- The 24v power supply is for the contactors.


Electrical layout & power
The crowd gate needs a 240v 20 amp breaker in your breaker panel to power it. From the breaker panel, an electrician-supplied 18 AWG 5-conductor cable runs to an electrician-supplied junction box. An included junction box sits at the front of the holding pen.
Run button cords up and away from moisture. The electrician-provided 5-conductor cord is needed to connect to the junction at the front of the holding pen.

Flat yellow cable conductor numbers
The flat yellow cable has its conductors numbered, printed on the inner insulation.
2 = L2
3 = Earth ground
4 = down button
5 = up button
6 = reverse button
7 = forward button
8 = button common
Pushbutton boxes & wiring
Each button uses 2 wires. Black can be the switch common, and Red is the input to the controller. The electrician supplies a 240v 20 amp breaker and the 18 AWG 5-conductor cable.
Front and rear button boxes
- Front buttons: the electrician supplies a junction box to connect button wires and a 5-conductor wire to go to the supplied junction box at the front of the holding area.
- Rear buttons: the electrician supplies a 5-conductor wire to go to the supplied junction box at the front of the holding area.

Prox connections
Blue is negative
Black is signal
Control buttons & LEDs
The board has control buttons and LEDs to help install, test, and troubleshoot:
- Control buttons on the board operate the gate directly for testing.
- Pushbutton LEDs illuminate when a button is pressed.
- Limit switch LEDs illuminate when a limit is against its stop.

Operating features
How hard the gate motor pushes is adjustable. The torque adjustment lets you set the max torque the gate uses. Cold weather takes more torque.
- Jog forward: press and release the Forward button to jog the gate forward for an adjustable amount of seconds. Each additional quick press and release of the Forward button adds additional time.
- Reversing: press Reverse and UP at the same time to make the gate go Up, then Back.
- Down jog: press and release Down quickly to jog the gate down.
Changing parameters
You can change numerous parameters to make your crowd gate operate correctly for your installation. The parameters are set on the VFD keypad.

To get into the Programming menu
- Press Back/Reset twice.
- Use the Up/Down arrows to put the arrow on the left of the screen to PAR.
- With the arrow at PAR, press OK. You are now in the Parameter menu.
- Press the Down arrow to scroll through the menu. (Left and Right arrows jump in big increments.)
To see or change a parameter
- Once you are at the parameter you want to see or change, press OK. (This displays the parameter’s value.)
- To change the value, press OK again. The value’s right-most digit should blink.
- While it’s blinking, use the Up and Down arrows to change it.
- Press OK when done to save it permanently.
To get out of the Parameter menu, press Back/Reset repeatedly.
Parameter reference
Parameters that need to be set
P1.4 – put to the motor nameplate amps. If torque is not high enough you will have to set it higher until it runs satisfactorily. Usually 1.5x the motor rating doesn’t harm the motor for short-duty-cycle applications like crowd gates.
Set the max torques to whatever you prefer. Test by using several people to push against it while it’s running.
| Parameter | Function | Notes |
|---|---|---|
| P17.1 | Down jog seconds | When you bump the down button, seconds it will run. Set the time it takes to lower most of the way. |
| P17.2 | Forward jogs seconds | When you bump the front button, seconds it will run. Set to about 1 side of parlor capacity. |
| P17.3 | Max consecutive jogs Down | Normally set to 1. |
| P17.4 | Max consecutive jogs Forward | Set to 1 if you don’t want employees to be able to bring it front really far by bumping rapidly. |
| P17.5 | Down Speed % | Speed going down. If you set P3.2 to 120 it will really go down fast. |
| P17.6 | Forward Speed % | Speed going front. If you set P3.2 to 120, lower this to 50% or less. |
| P17.7 | Reverse Speed % | Speed going reverse. If you set P3.2 to 120 it will really go back fast. |
| P17.8 | Up Speed % | Speed going up. If you set P3.2 to 120, lower this to 50% because it runs out of power. |
| P17.9 | Max Down torque % | Max torque till overloading going down. |
| P17.10 | Max Forward torque % | Max torque till overloading going Forward. |
| P17.11 | Max Reverse torque % | Max torque till overloading going reverse. |
| P17.12 | Max UP torque % | Max torque till overloading going UP. |
| P17.13 | Max torque while starting % | Torque override while the motor is starting. |
| P17.14 | Starting torque seconds | Motor-is-starting duration. |
| P17.15 | Gate lifting seconds | Time for the gate to lift using air. |
| Parameter | Function | Notes |
|---|---|---|
| P18.1 | Up/Down mode | 0 = motorized, 1 = air powered, 2 = up/down not used. |
| P18.2 | Enable home delay | Set to 1 if the gate just wants to drift off of the up limit while homing. |
| P18.3 | Enable reverse jogging | Set to 1 to be able to send the gate to back without lifting by long pressing reverse. |
| P18.4 | Digital output function | 0 = motor selector, 1 = for/rev brake, 2 = travel alarm, 3 = down air solenoid, 4 = up air solenoid. |
| P18.5 | Relay 1 function | See P18.4. |
| P18.6 | Relay 2 function | See P18.4. |
| P18.7 | Seconds for long press | Long press seconds for reverse jog and back limit defeat. |
| Parameter | Function | Notes |
|---|---|---|
| P1.4 | Motor Amps – Defines 100% torque | Dictates what 100% torque is. Set to the motor nameplate amps. |
| P3.2 | Max frequency – Defines 100% speed (60–120hz) | Setting it too high just causes overloads. |
Diagnostic monitor reference
To access the Diagnostic menu
- Press Back/Reset twice.
- Use the Up/Down buttons to move the arrow to MON.
- Press OK.
- Press the Right key till you get to 5.1.
- Press Down to scroll and find the diagnostic register you want.
- Press OK to see the results.
| Monitor | Reads | Notes |
|---|---|---|
| 1.5 | Motor % torque | Use it to figure out where the max torque settings should be for your installation. |
| 5.1 | Is UP button on or off | 0 = off, 1 = on. Use it to decide if a button is stuck. |
| 5.2 | Is Down button on or off | 0 = off, 1 = on. Use it to decide if a button is stuck. |
| 5.3 | Is Front limit on or off | 0 = off, 1 = on. Use it to decide if it works. |
| 5.4 | Is Back limit on or off | 0 = off, 1 = on. Use it to decide if it works. |
| 5.5 | Is UP limit on or off | 0 = off, 1 = on. Use it to decide if it works. |
| 5.6 | Is Down limit on or off | 0 = off, 1 = on. Use it to decide if it works. |
| 5.7 | Is Forward button on or off | 0 = off, 1 = on. Use it to decide if a button is stuck. |
| 5.8 | Is Reverse button on or off | 0 = off, 1 = on. Use it to decide if a button is stuck. |
| 5.9 | Number of forward presses | In V8 this register seems to count too many. |
| 5.10 | Number of reverse button presses | Resets every time the power goes out. |
| 5.11 | Number of UP button presses | Resets every time the power goes out. |
| 5.12 | Number of Down button presses | Resets every time the power goes out. |
| 5.13 | Number of front limit cycles | Resets every time the power goes out. |
| 5.14 | Number of back limit cycles | Resets every time the power goes out. |
| 5.15 | Number of up limit cycles | Resets every time the power goes out. |
| 5.16 | Number of down limit cycles | Resets every time the power goes out. |
| 5.17 | Number of overloads | Resets every time the power goes out. |
| 5.18 | Average torque Up | Developer feature. |
| 5.19 | Average torque Down | Developer feature. |
| 5.20 | Average torque Forward | Developer feature. |
| 5.21 | Average torque Reverse | Developer feature. |
Wiring schematics
240v wiring
Wiring theory: 240v single phase comes from the festoon cable into the bottom of the breaker. 240v power goes to 4 places: the VFD, the brake, and both power supplies. All gate control logic is done with a custom firmware loaded at the time of manufacture.
The VFD’s relay 1 controls the (2) 24vdc coil contactors. These relays both turn on when the Up/Down motor is engaged. The 3 pole relay connects the VFD to the correct motor, and the 2 pole releases the brake. The Up/Down motor uses 12 AWG; the brake is wired with 14 AWG.

Internal control wiring
The internal control wiring connects the custom VFD’s control terminals to the PCB and the relays.

Parts list

| Item | Part number / detail |
|---|---|
| DC board PCB | PCB134v2 |
| 5v power supply | RS15-5 |
| 24v power supply | RS15-24 |
| Wifi radio | HCG-O2 |
| USB extension | HCG-03 |
| Beeper | HCG-O1 |
| Remote control computer assembly | HCG-04 |
| RS485 cable | HCG-05 |
| Custom VFD | HCG-100v2 |
| 2 pole breaker 20 amp | DB20A2PDIN7 |
| 2 pole relay 24vdc | Relay: 782-2C-24D / Socket: 782-2C-SKT |
| 3 pole relay 24vdc | Relay: 783-3C-24D / Socket: 783-3C-SKT |
| Pushbutton (solid state) | PN# PushBCG (upgraded to solid state switching) |
| Pushbutton (deprecated) | PN# MPP00014 (normally open) |
| 22mm pushbutton | PN# PushB22MR (rubber cover & green contact block) |
| Stainless pushbutton plate | PN# HCG-401 (legend lasered, holes for 4 buttons) |
| 4 button enclosure (22mm holes) | PN# SA109-40SL (without labels or buttons) |
| Complete 4 button enclosure | PN# HCG-BRB04 (22mm holes, with labels, buttons, and 1 meter male M12) |
Troubleshooting
If the gate does not respond to the pushbuttons
- Press the pushbuttons at all operator locations. If the pushbutton LEDs don’t illuminate, check the wires going to the pushbuttons.
- Press the control buttons on the board. If the on-board buttons activate the gate, the wires going to the pit or rear of the holding area have a problem.
- Make sure the VFD is in IO mode. Press Loc/Rem and watch the arrow on the bottom of the screen. Make sure the arrow is above IO. Gate control will not work when the arrow is above Hand.
- If a pushbutton LED stays illuminated all the time, check the cables or for water in a button box.
- If a limit LED is on all the time, cycle the limit to make sure it’s not stuck. The limit switch should click when moved.
- If a limit LED never turns on, check the connections in the limit.
If the forward/reverse motor runs all the time
If the forward/reverse motor runs all the time, even when the up/down motor is to be running, check to make sure the 3 pole relay is switching on when the Up/Down button is pressed. If it’s not, inspect the contactor and check if it’s getting 24vdc.
Specifications
| Power in | 240v 20 amp single phase (needs a 240v 20 amp breaker) |
|---|---|
| Drive | Custom VFD (HCG-100v2) |
| Motors | Up/Down motor (12 AWG) and Forward/reverse motor; brake (14 AWG) |
| Control supplies | 5v (RS15-5) for wifi; 24v (RS15-24) for contactors |
| Relays | 3 pole relay 24vdc (783-3C-24D) for motor selection; 2 pole relay 24vdc (782-2C-24D) for the brake |
| Button cable | Electrician-supplied 18 AWG 5-conductor |
| Limit switches | Normally open |
| Connectivity | Wifi radio and setup screen; Farmshield.net remote diagnostics |