CAPTAIN 6 Dairy & Livestock Ventilation Controller – Setup & User Guide

Wiring, sensors, and the parameter reference for the AutoVent CAPTAIN 6 dairy and livestock ventilation controller. Version 20.1 (v201).

Model AV6
10 relay outputs
Touch screen
THI cow-comfort index
Soakers & VFD ready

AutoVent CAPTAIN 6 dairy controller terminal block with the Temperature probe #1 terminals circled in red, alongside wind sensor terminals 96 to 99, Rain sensor #1, 0-10v, Sensor #4, Sensor #3 and 24 vdc connections

The CAPTAIN System

Thank you for purchasing the CAPTAIN System. It is designed for easy installation and operation. The system is designed to control curtains, heaters, and fans. The CAPTAIN System is designed for the unique challenges of dairy and animal facilities.

Main features

  • Temperature sensor
  • Wind speed sensor option
  • Humidity option
  • Battery-backed clock
  • 10 relay outputs
  • Adjustable temperature settings
  • Touch screen display
  • Manual overrides

Installing the CAPTAIN

Consider the following before installing the CAPTAIN:

  • Protect the enclosure from moisture – mount it in a secure and dry place.
  • Important: only drill holes in the bottom of the enclosure.
Warning: condensation runs downhill. Drilling holes into the top or upper sides of the enclosure voids the warranty.

Wiring the temperature sensor

Place the temperature sensor in the middle of the building, or in a location that represents the building’s average temperature. It is important to not allow sensors to come into contact with direct sunlight.

Connect the temperature sensor to the Sensor #1 terminals. Polarity is not important.

CAPTAIN 6 terminal block diagram with the Temperature probe #1 terminals circled in red, alongside wind sensor terminals 96 to 99 and pulse, Temperature probe #2, 24 vdc, 0-10v, Sensor #4, Rain sensor #1 and Sensor #3 connections
Connect the temperature probe to the Sensor #1 (Temperature probe #1) terminals, circled in red.

Extending the temperature sensor

  1. Run 18–22 AWG wire (twisted or shielded wire if possible) from the sensor to the CAPTAIN. Keep the sensor wire away from high-voltage wire by at least 1 foot. Specifically, keep it away from the VFD output wires.
  2. Solder or use gel-filled crimps to connect your wires to the temperature sensor.

Connecting the wind meter

The wind meter is used to close curtains or shut off fans in high-wind conditions. CAPTAIN series controls do not sense wind direction, so it responds no matter which direction the wind comes from. Use 18–24 AWG wire.

Wiring diagram for the CAPTAIN 6 cup-style anemometer showing the white, black and red wires running from the wind sensor to the controller terminals 96 to 99 and 24v aux using 18 to 24 AWG wire
Wind meter wiring to the CAPTAIN 6. Use 18–24 AWG wire.
Red wire → 24v +
White wire → 99 (pulse)
Black wire → 98 (Negative / 0V)

Connecting a rain sensor

You can connect a rain sensor to the system. The rain sensor closes select vent motors when it is raining. The system supports up to 3 rain sensors.

If you connected a rain sensor, the controller needs to know it. Setup parameters P40 & P41 assign the sensor to the vent motors.

Installing the rain sensor

When you are installing the wires, keep the rain sensor cord 6 inches away from high-voltage wires. The vent motor’s close signal is activated when the sensor is wetted. The position of the sensor versus the sky dictates the response.

Rain sensor mounting diagram showing the sensor on a mast tilted toward the sky, with arrows marking a more-sensitive vertical position and a less-sensitive angled position beneath a rain cloud
The position of the sensor relative to the sky sets its response: more vertical is more sensitive, tilted away is less sensitive.
Rain sensor wiring diagram showing the white, brown, blue and black wires landing on the CAPTAIN 6 Rain sensor #1 terminals, with the dome sensor connected below the board
The wire colors are marked on the board and match the sensor’s cord. Wire by connecting the colors.

Connecting a humidity sensor

The humidity sensor allows you to monitor and control the humidity. If humidity is too high, a vent can open or a fan can start. If you connect a humidity sensor, it needs to be activated. Activate it by selecting humidity for setup parameter P10.

Location of the humidity sensor

Mount in a central location. Keep the sensor away from heaters, or you will get a low reading when the heater is running.

Installing the humidity sensor

Route humidity sensor wires 6 inches away from high-voltage wires.

Humidity sensor wiring diagram showing the blue wire to 24v aux power and the black wire to Sensor #3 plus on the CAPTAIN 6 board
Humidity sensor wiring to the CAPTAIN 6 board.
Blue wire → Power 24v +
Black wire → Sensor #3 +

Powering the CAPTAIN

  • AC versions come with a power cord. Plug it into a 120v outlet. Requires 120V, 5 amp.
  • DC solar versions require 12VDC. Momentary maximum of 20 amps.

Connecting to ventilation equipment

The relay has 3 rows of terminals where you connect ventilation equipment. The bottom row is numbered for the corresponding relay number.

  • The top row is Normally open.
  • The middle row is Normally closed.
  • The bottom row is Common.
Photo of the CAPTAIN 6 relay board with plug-in relays above three rows of output terminals; the Normally open and Normally closed rows are circled in red and the bottom common output terminals are labeled
The three terminal rows: Normally open (top), Normally closed (middle), and Common (bottom output terminals).

Motor connector bus bars

The bus bars are aluminum strips that are intended to make it easy for low-voltage vent motors. They can be shortened or removed to allow fans, heaters, or lights to be connected instead of vent motors. To shorten them, remove the connector completely and use pliers to bend it repeatedly to break it apart.

Photo of the CAPTAIN 6 relay board with the low-voltage motor power bus bars circled in red across the output terminals
The low-voltage motor-power bus bars (circled) on the relay board.
Photo of two aluminum bus bar connector strips removed from the CAPTAIN 6 board
The aluminum bus bar connector strips.
Close-up CAPTAIN 6 wiring detail with the left bus bar and the right common jumpers circled in red above output terminals numbered 6 through 1
Detail of the bus bar (left) and the common jumpers (right) above outputs 6 through 1.

Connecting DC motors

The CAPTAIN6PS includes a 10-amp 24v motor supply. It is prewired to run several DC vent motors. Each has a circuit breaker to protect the motors. Connect motors directly to the board as shown (connector bars installed).

Wiring diagram for 24vdc vent motors connected to CAPTAIN 6 outputs 6 through 1 with curtain motor circuit breakers above, terminal rows labeled A normally open, C normally closed and B common
24vdc vent motors connected directly to the board (connector bars installed).

Curtain motor circuit breakers

There are several curtain motor breakers. Each of them protects a motor. If a motor’s amps go too high, the center tab trips out. Press the tab in to reset.

Connecting AC vent motors

120v AC vent motors can be run directly from the board as long as they are 1/3 hp or less.

Relay #1 = Curtain 1 close signal
Relay #2 = Curtain 1 open signal
Relay #3 = Curtain 2 close signal
Relay #4 = Curtain 2 open signal
Relay #5 = Curtain 3 close signal
Relay #6 = Curtain 3 open signal

(This assumes P1 Curtain start relay is set to 1.)

Wiring diagram for a 120v cable pull machine connected to CAPTAIN 6 outputs with close and open signals, plus 120v hot, neutral and ground run from a breaker panel
A 120v cable pull machine wired to the open and close relay outputs, with hot, neutral, and ground from the breaker panel.

Connecting to heaters

Typical heater wiring connections to the control are shown below.

Wiring diagram showing two GreenGro 120 heaters connected to CAPTAIN 6 relay outputs by a control signal, with 120/240v power supplied from a breaker panel
Typical heater wiring: the control switches the heaters via a control signal; line power runs separately.

Connecting fans

The relay outputs are pilot duty. Do not try running fan motor current through the relay or it will burn out. Use a contactor to switch the fan’s electricity. The controller will simply switch the contactor on and off.

Wiring diagram showing CAPTAIN 6 relay outputs switching an AutoVent 2-zone SPST 25-amp contactor box that powers the fans, with the line power fed from a breaker panel
Fans switched through an AutoVent 2-zone SPST 25-amp contactor box; the relay only switches the contactor.

Connecting variable-speed fans

0-10v VFDs can be connected and their speed controlled automatically by temperature. VFDs use 2 signals: a speed signal and a start signal. Wiring consists of both of these signals, which always takes at least 4 conductors.

The speed signal is dc voltage which varies between 0–10v. 10v is 100% speed; 0 = stopped (but still energized). The start signal is a Normally Open switch to tell the VFD when to energize the motor.

Multiple VFDs can be connected in series. The maximum varies by brand. The limit varies between 5 and 50 VFDs. AutoVent brand VFDs have a max of 50.

Configuration needed to match this diagram: P2 Number of fans = 1, P3 Starting relay for fans = 6, P17 0-10v output enabled = 1.
Wiring diagram for a 0-10v variable-speed fan showing the analog speed signal and start signal running from the CAPTAIN 6 outputs to an AutoVent VFD
0-10v variable-speed fan wiring to an AutoVent VFD, with the matching setup parameters.

Connecting Lenze ACtech VFDs

Wiring diagram for a Lenze ACtech SMV vector VFD connected to a CAPTAIN 6, showing the 0-10v analog positive and negative, forward and switch common terminals, with the Captain 6 and Actech configuration values listed
Lenze ACtech SMV vector VFD wiring. CAPTAIN 6 config: P2 = 1, P3 = 6, P17 = 1. Actech settings: P100 Start source = 1 (remote), P101 Standard Reference = 1.

Reconfigurable outputs

Fans, heaters, lights, and curtain motors can be mapped to any relay. The only limitation is that multiples of an equipment type use consecutive relays.

Example: if there are 4 fans (as per parameter P2), and the fan’s start relay is 1 (parameter P3), relays 1 through 4 will be the fan circuits.

Screen overview & overrides

The screen shows you what is happening. You can see the temperature and the status of the relays. Press on the temperature to go to your settings. Press the bottom row of buttons to manually override.

CAPTAIN 6 touch screen status view showing the time 1:41, No Rain, minus 35 degrees, 0.0 MPH, and Auto vent open and close buttons for Vent 1 to Vent 4 with Fan 1 and Fan 2, with Vent 3 close highlighted green
The status screen shows temperature, wind speed, rain status, and the per-relay override buttons.

Overrides

Select the relay status you want. In Auto, it will operate automatically. Selecting Off or Forced allows you to avoid the control system. To exit, press the blank space on the sides.

CAPTAIN 6 override screen for Output 2 Fan number 2 showing the auto button highlighted green above the off and forced on buttons
The override screen for an output: Auto (green), Off, or Forced on.

Parameter reference

There are parameters that you can change. The parameters are labeled P1, P2, and so on. These parameters are the temperature setpoints and values you can adjust. From the parameter screen you can scroll to other parameters and edit each parameter ID.

CAPTAIN 6 parameter editing screen showing parameter ID P31 summer start set to 65 degrees, with Prior and Next scroll buttons, minus and plus value buttons, and Exit menu and Save buttons
The parameter editing screen: scroll with Prior/Next, adjust the value, and Save.

Curtain parameters

Curtain parameters
IDDescriptionDefaultMinMax
P101–P103Open temperature for Curtain #1 – Curtain #10.60°1°99°
P131–P133Curtain #1 – Curtain #3’s run seconds. How many seconds the curtain runs per interval.15  
P141–P143Curtain #1 – Curtain #3 pause minutes. The time the curtain waits between intervals.50  
P151–P153Curtain #1 – Curtain #3 ventilation temperature gap. The difference between open and shut temperature.50  
P170Curtain motor’s max humidity. Humidity at which the curtain will open to dry things.95  
P171Seconds the curtain will open for the humidity event.10  
P172Humidity limits temperature. Humidity will be disregarded if it is too cold.32  
P181–P190Curtain #1 – Curtain #10 sequence. If vent should wait on another curtain to close first from rain or high wind.0  
P191–P200Curtain #1 – Curtain #10. How long it takes a curtain to shut. Closing seconds for rain or high-wind events.100  
P201High-wind vents – which vents should shut from wind.0  
P202High wind MPH.53  
P203Wind override clear MPH.50  

Fan temperature parameters

The temperature parameters control the starting temperature. The fans are used for cooling. They will turn on above the temperature setpoint. If humidity is connected, fan #1 can be set to clear out the high humidity.

Fan temperature parameters
IDDescriptionDefaultMinMax
P301–P306Start temperature for Fan #1 – Fan #6.0°1°99°
P331Fan temperature gap. Difference between on and off.0.3  
P341Fan max MPH. If wind sensor is connected, MPH at which fans will stop.0  
P342MPH deadspan.0  
P350Fan #1 max humidity. If humidity sensor is installed, when fan #1 will start to dry out the building (set to 101% to disable humidity function).99%RH  
P351Fan humidity hysteresis.5% 101
P352Fan humidity low-temperature limit.32°  
P361–P366Fan #1 – Fan #6’s high-temperature limit.0  

THI index

The THI index uses the average temperature and the humidity to turn the fans on sooner. This allows the controller to think more like a cow. You can adjust how much humidity and high temperatures affect the index.

Two CAPTAIN 6 screens side by side: a status screen at 16:56 showing 75.6 degrees, 69.0 degrees, 26 percent RH, 0.0 MPH with Fan 1, Fan 2 and Fan 3 buttons; and a THI detail screen showing 73.8 degrees effective temperature, 66.7 degrees 8 hour average, 0 percent RH adding 0.0 degrees, and 75 degrees average will add 6 degrees
THI in action: the effective temperature combines the rolling average temperature with humidity to start fans sooner.
THI index parameters
IDDescriptionDefaultMinMax
391If THI index should be enabled. 0 = no, 1 = temperature based only, 2 = humidity and temperature based THI.002
P392Hot temperature trigger, i.e. how high is the average temperature to be considered hot?75°1°99°
P393How many degrees are added to the effective temperature when it’s hot.6°1°20°
P394How many hours are included in the rolling temperature average.8124
P395Optional – when humidity starts affecting the effective temperature.60%RH10%95%
P396At 99% humidity – how much the humidity will be adding to the effective temperature. This effect tapers to zero at P396 humidity.6°020

Variable fan parameters

Controlling the speed signal

The VFD will run at the minimum speed when the temperature reaches the “start temperature.” As the temperature continues to rise the VFD will run faster until it reaches 100% speed. The VFD is at 100% speed when the temperature reaches “Max speed.”

You can add 2 additional 0-10v zones with a KVT-EX02 expansion module. P17 sets the number of zones you wish to use.

CAPTAIN 6 variable fan speed screen showing 16 percent speed at a 65 degree start, 80 degrees is full speed, and a note that speed changes automatically by temperature
The variable fan speed screen: speed ramps with temperature between the start temperature and full speed.
Variable fan parameters
IDDescriptionDefaultMinMax
P401Low-speed temperature for variable fans.50°1°99°
P402High-speed temperature for variable fans.85°  
P403Low speed for variable fans.20  
P404Manual speed for variable fans.11199°
P405Fan speed if humidity is high.98  
P410Optional Zone 2 low-speed temperature for variable fans.50°1°99°
P411Optional Zone 2 high-speed temperature for variable fans.85°  
P412Optional Zone 2 low speed for variable fans.20  
P413Optional Zone 2 manual speed for variable fans.11199°
P405Optional Zone 2 fan speed if humidity is high.98  
P420Optional Zone 3 low-speed temperature for variable fans.50°1°99°
P421Optional Zone 3 high-speed temperature for variable fans.85°  
P422Optional Zone 3 low speed for variable fans.20  
P423Optional Zone 3 manual speed for variable fans.11199°
P425Optional Zone 3 fan speed if humidity is high.98  
P429Variable speed off mode. When temperature is below P401 the speed signal will be: 0 = minimum speed / P403, 1 = off.001

Light timer

The lights are a simple time clock that goes on and off based on the time you enter. It is based on 24-hour time in 6-minute intervals.

Light timer parameters
IDDescriptionDefaultMinMax
P560Time on for lights, Period A.0.000:0424:00
P561Time off for lights, Period A.0.000:0424:00
P562Time on for lights, Period B.0.000:0424:00
P563Time off for lights, Period B.0.000:0424:00

Heater parameters

The parameters control the starting temperature.

Heater parameters
IDDescriptionDefaultMinMax
P601–P610Heater 1 – Heater 10’s setpoint°.60°1°100°
P631Heater hysteresis.2.0°  

Duty cycle fan

The duty cycle fan was intended to control a fan to provide a variable amount of air by stopping and starting it. You can set how long the cycle is to keep it from cycling too often. Cycling too often will prematurely wear the contacts and your motors.

Duty cycle fan parameters
IDDescriptionDefaultMinMax
P850Start temperature. However, a 0 means it’s on always to maintain minimum ventilation. Note: to keep it from short cycling, above 95%, the fan will be on regardless.40°1°100°
P851Begin accelerating temperature.60°1°100°
P852Always on temperature. The duty cycle is at 100% and the fan will not turn off.801120°
P853Minimum %. The least amount the duty cycle fan will be on.10%5%100%
P854Cycle minutes. How long an on/off cycle will be.3120

Soakers

The soakers function by turning a valve on and off. The spray and dry-off times ramp between setpoints to give you an infinitely adjusted water output. For reduced water demand, each zone takes turns spraying. It controls up to 6 individual soakers. The amount of water used and how often it sprays is controlled by the temperature or temperature index.

Sprinkler temperature settings

The spray time ramps between low and high spray seconds with the barn temperature. The first zone has its own spray seconds. The remaining zones share spray settings.

The dry-off / interval time ramps between low and high dry-off minutes with the barn temperature. All zones share the dry-off minutes. The interval time is the amount of time each zone waits between sprinkles.

In the eastern USA, it is typical to spray for about 30–60 seconds. This varies with the spray tip size. The goal is to get the cow wet but not running onto her udder. When the side of the leg is wet, it is time to stop.

Application note: a 100 lb cow, laying in a forestall, will overheat within 90 minutes at 5 MPH @ 90° @ 70%RH. Getting a cow’s body temperature down from 102° to 100° takes 5 cycles. This means a theoretical 25 minutes at 90°. If the cow is drying off before 5 minutes in very hot weather, a 3-minute high dry-off time gets her cooled down in 15 minutes. The dry-off time usually is 15 minutes at 70° and 5 minutes at 90°.
Soaker parameters
IDDescriptionDefaultMinMax
P800Soaker start temperature.75°1°99°
P801Soaker high temperature.95°1°99°
P802Soaker dry-off minutes when the temperature is at the start temperature.15125
P803Soaker dry-off minutes when the temperature is at the high temperature.5125
P804Spray seconds at low for zone #1.301250
P805Spray seconds at high for zone #1.301250
P806Spray seconds at low for zone #2–6.301250
P807Spray seconds at high for zone #2–6.301250

Setup configuration

Setup configuration parameters
IDDescriptionDefaultMinMax
P0Number of curtains.203
P1Curtain starting relay.101
P2Number of fans in the system.106
P3Fan starting relay.506
P4Number of heaters.2 6
P5Heater starting relay.8 6
P6Number of grow lights.011
P7Grow lights starting relay.1 6
P8Number of sprinkler circuits.006
P9Starting relay for the sprinklers.116
P12Duty cycle fan enabled. 0 = no, 1 = yes.0 1
P13Duty cycle fan relay.0 6
P16If 0-10v zone 1 should use humidity instead of temperature. 0 = No, 1 = Yes.001
P17Number of 0-10v zones in system.013
P180-10v low-temperature volts. Normally this is zero unless you want 10v to shut the fan off.0010
P190-10v high-temperature volts. Volts at high temperature.10010
P20Is 2nd temperature sensor enabled.0  
P21Is humidity sensor enabled.0  
P22Temperature probe 1 offset.0.0-10.0+10.0
P24Fahrenheit or Celsius. 0 = F, 1 = C. If set to 1, wind will display as KPH.F  
P27Wind response time minutes.3  
P28Anemometer calibration. 17 for KPH.252 
P29Wind meter enabled.0  
P30Revert controller to defaults.315
P41–P49Curtain #1 – Curtain #3 rain sensor uses input #. You select which input a curtain’s rain sensor is connected to.0  
P60Fan high-temperature shutoff enabled? 0 = no, 1 = yes.   
P61–P70Turn fan 1 – fan 10 input off.0  
P71How many curtains use 2nd temperature sensor.0  
P72How many heaters use 2nd temperature sensor.0  
P73How many fans use 2nd temperature sensor.0  

Specifications

CAPTAIN 6 dairy controller specifications
Size of enclosure7″ × 10″ × 6″
Input voltage120 VAC
Output10 Normally open relays
Temperature sensorThe 3-foot cord can be extended to 100 ft.
Warranty1 year

← Back to all manuals