CAPTAIN 10 (AV10PS) Dairy & Livestock Ventilation Controller – Setup & User Guide

Wiring, sensor setup, and the complete parameter reference for the AutoVent CAPTAIN 10 dairy and livestock controller. Version 215.

Model AV10PS
10 relay outputs
Touch screen
THI cow-comfort index
Soakers & cool cells

AutoVent CAPTAIN 10 dairy controller terminal block with the Temperature probe #1 terminals circled in red, alongside wind sensor terminals 96 to 99, rain sensor, 0-10v, Sensor #3, Sensor #4 and 24 vdc connections

System overview

Thank you for purchasing the CAPTAIN System. It is designed for easy installation and operation. The system is designed to control curtains, heaters, and fans.

The CAPTAIN System is designed for the unique challenges of dairy and animal facilities. It connects to curtains, fans, heaters, soakers, and weather sensors, then uses temperature, humidity, and time-of-day rules to keep the barn comfortable for the herd.

Main features

  • Temperature sensor
  • Wind speed sensor option
  • Humidity option
  • Battery-backed clock
  • 10 relay outputs
  • Adjustable temperature settings
  • Touch screen display
  • Manual overrides

Installing the CAPTAIN

Consider the following before installing the Captain:

  • Protect the enclosure from moisture – mount it in a secure and dry place.
  • Important: only drill holes in the bottom of the enclosures.
Warning: condensation runs downhill. Drilling holes into the top or upper sides of the enclosure voids the warranty.

Wiring the temperature sensor

Place the temperature sensor in the middle of the building or in a location that represents the building’s average temperature. It is important not to allow sensors to come into contact with direct sunlight.

Connect the temperature sensor to the Sensor #1 terminals. Polarity is not important.

CAPTAIN 10 terminal block with the Temperature probe #1 terminals circled in red, next to wind sensor terminals 96 to 99 and pulse, Temperature probe #2, 24 vdc, 0-10v, Sensor #4, Rain sensor #1 and Sensor #3 connections
Connect the temperature probe to the Sensor #1 (Temperature probe #1) terminals, circled in red.

Extending the temperature sensor

  1. Run 18–22 AWG wire (twisted or shielded wire if possible) from the sensor to the Captain. Keep the sensor wire away from high-voltage wire by at least 1 foot. Specifically, keep it away from the VFD output wires.
  2. Solder or use gel-filled crimps to connect your wires to the temperature sensor.

Connecting the wind meter

The windmeter is used to close curtains or shut off fans in high wind conditions. Use 18–24 AWG wire.

Wiring diagram for the CAPTAIN 10 anemometer showing the white, black and red wires running from a cup-style wind sensor to the controller terminals 96 to 99 and 24v aux using 18 to 24 AWG wire
Wind meter wiring to the CAPTAIN 10. Use 18–24 AWG wire.
Red wire → 24v +
White wire → terminal 99 (pulse)
Black wire → terminal 98 (Negative/0V)

Captain series controls don’t sense wind direction, so they respond no matter which direction the wind comes from. Non-directional wind sensing is more useful for greenhouses than livestock.

For naturally ventilated barns: if you want to regulate the wind for livestock, we recommend upgrading to the KVT-400 control. It uses wind direction to do an excellent job with naturally ventilated livestock barns.

Connecting a rain sensor

You can connect a rain sensor to the system. The rain sensor closes select vent motors when it’s raining. The system supports up to 3 rain sensors.

If you connected a rain sensor, the controller needs to know it. Setup parameters P41 thru P45 assign the sensor to the curtain motors.

Installing the rain sensor

When you are installing the wires, keep the rain sensor cord 6 inches away from high-voltage wires. The vent motor’s close signal is activated when the sensor is wetted. The position of the sensor versus the sky dictates the response.

Rain sensor #1 wiring diagram showing the white, brown, blue and black wires landing on the CAPTAIN 10 board, with the sensor mounted on the side of a building
Rain sensor #1 wire colors are marked on the board and match the sensor’s cord. Wire by connecting the colors. Tilting the sensor toward the sky makes it more sensitive; tilting it away makes it less sensitive.

Adding a 2nd and 3rd rain sensor

The wire colors are marked on the board and match the sensor’s cord.

Rain sensor #2
White —- Input: #2
Brown —- Input: Common
Black —- black – rain sensor #1
Blue —- blue – rain sensor #1Rain sensor #3
White —- Input: #3
Brown —- Input: Common
Black —- black – rain sensor #1
Blue —- blue – rain sensor #1
CAPTAIN 10 relay board photographed with three dome rain sensors labeled Rain #1, Rain #2 and Rain #3 wired back to the sensor input terminals
Up to three rain sensors (Rain #1, Rain #2, Rain #3) wired to the controller’s sensor inputs.

Rain sensor DIP switches

The sensor has 4 sensitivity settings. Dip switches 1 & 2 set the rain detect threshold.

Close-up photo of the rain sensor circuit board showing the bank of DIP switches labeled On at the top and Off at the bottom
The DIP switch bank inside the rain sensor (On at top, Off at bottom).
Rain sensor DIP switch table
SwitchSetting
1Sensitivity (default off)
2Sensitivity (default ON)
3Off (15-minute reopen delay when on)
4Must be off
5Must be ON
6Must be off
7Must be off
8Must be off

Sensitivity settings (switches 1 & 2)

Rain detection thresholds
Switch 1Switch 2ThresholdNotes
OffOffFirst-drop detectionVery sensitive; will be on at first drop of rain. Our experience is this might close vents too quickly. Potential exists for false alarms.
OnOff0.1 inch per hourSensitive – about right for some buildings.
OffOn0.25 inch per hourModerate response. This works well for most general applications.
OnOn1 inch per hourThis will have everything soaked before closing.

15-minute delay after it stopped raining: normally the vent needs to reopen after it stopped raining. If you want it to stay closed for a while after the rain, set DIP switch 3 on. Normally we want #3 off, so vents re-open sooner.

Connecting a humidity sensor

The humidity sensor allows you to monitor and control the humidity. If humidity is too high a vent can open or a fan can start. If you connect a humidity sensor, it needs to be activated. Activate it by selecting humidity for setup parameter P10.

Location of the humidity sensor

Mount in a central location. Keep the sensor away from heaters or you will get a low reading when the heater is running.

Installing the humidity sensor

Route humidity sensor wires 6 inches away from high-voltage wires.

Humidity sensor wiring diagram showing the AutoVent humidity sensor blue wire to Power 24v plus and the black wire to Sensor #3 plus on the CAPTAIN 10 board
Humidity sensor wiring to the CAPTAIN 10 board.
Blue wire → Power 24v +
Black wire → Sensor #3 +

Powering the CAPTAIN

Requires 120V or 240v. Load is 5 amps for 120v and 2.5 for 240v.

Photo of the CAPTAIN power supply terminal block with the 120v incoming Hot, Neutral and Ground wires landed on the labeled terminals
If powered by 120v: Hot, Neutral, and Ground to the supply terminals.
Photo of the CAPTAIN power supply terminal block wired for 240v with the Ground, L1 and L2 conductors landed on the labeled terminals
If powered by 240v: Ground, L1, and L2 to the supply terminals.

Connecting to ventilation equipment

The relay board has 3 rows of terminals where you connect ventilation equipment. The bottom row is numbered for the corresponding relay number.

  • The upper row is Normally open.
  • The middle row is Normally closed.
  • The bottom row is Common.
Photo of the CAPTAIN 10 relay board with ten plug-in relays above the output terminals, labeled Upper, Middle and Bottom for the three terminal rows
The three output terminal rows: Upper (Normally open), Middle (Normally closed), and Bottom (Common).

24v motor connector bus bars

The bus bars are aluminum strips that are intended to make it easy for low-voltage vent motors. They can be shortened or removed to allow fans, heaters, or lights to be connected instead of vent motors. To shorten them, remove the connector completely and use pliers to bend it repeatedly to break it apart.

Photo of the CAPTAIN 10 output terminals with the aluminum 24v motor bus bars circled in red across the relay output rows
The 24v motor connector bus bars (circled) feed low-voltage motors directly from the board.
Close-up photo of two aluminum bus bar connector strips on the output terminals, circled in red
The aluminum bus bar connectors, circled.

Connecting DC motors

The CAPTAIN10 PS includes a 20-amp 24v motor supply. It is prewired to run several DC curtain motors. Each has a circuit breaker to protect the motors. Connect motors directly to the board as shown (connector bars installed).

Curtain motor circuit breakers

There are several curtain motor breakers. Each of them protects a motor. If a motor’s amps go too high, the center tab trips out. Press the tab in to reset.

There can be 5, 7.5 & 10 amp breaker sizes shipped with the controller for 24v motors. For best fabric protection use the smallest amp that doesn’t nuisance trip.

Wiring diagram for four DC curtain motors connected to the CAPTAIN 10 relays 1 through 8, with the Normally open and Normally closed terminal rows, per-motor circuit breakers, and an optional 5th curtain on relays 9 and 10
Four DC curtain motors wired to relays 1–8, with the optional 5th curtain on relays 9 and 10 if jumpers are extended onsite.

Configuration needed to match this diagram:

  • P0 Number of curtains = 4
  • P1 Curtain starting relay = 1
  • P2 Number of fans = 0
  • P4 Number of heaters = 2
  • P5 Heater starting relay = 9
  • P6 Number of lights = 0
  • P8 Number of soakers = 0
  • P17 0-10v enabled = 0

Relay assignments for this diagram: Relay #1 = Curtain 1 close signal, Relay #2 = Curtain 1 open signal; Relay #3 = Curtain 2 close, Relay #4 = Curtain 2 open; Relay #5 = Curtain 3 close, Relay #6 = Curtain 3 open; Relay #7 = Curtain 4 close, Relay #8 = Curtain 4 open.

Wiring diagram showing two GreenGro heaters fed by their control signal and 120/240 power, plus four cable-pull vent motors wired to the CAPTAIN 10 relay outputs with open and close conductors
Two staged heaters plus four cable-pull vent motors on the relay outputs.

Connecting AC vent motors

Small 120v AC vent motors can be run directly from the board as long as they are 1/4 hp or less.

Disconnect the DC motor power supply by insulating the Blue and Purple wires feeding the circuit board.

Connecting AC fans

Always use contactors to run fans. The controller will switch fan contactors on and off. In most installations, many fan contactors can be connected to a single relay.

Do not try powering a fan motor directly thru a relay. It will burn out.
Wiring diagram for AC exhaust fans run through Fan #1 and Fan #3 contactors fed from the breaker panel and switched by CAPTAIN 10 relays 9 and 10, with two vent motors on the right-hand relays
AC fans switched through contactors. High voltage for the fans comes from the breaker panel; the controller only switches the contactor coils.

Configuration needed to match this diagram:

  • P0 Number of curtains = 2
  • P1 Curtain starting relay = 1
  • P2 Number of fans = 3
  • P3 Fan starting relay = 8
  • P4 Number of heaters = 0
  • P6 Number of lights = 0
  • P8 Number of soakers = 0
  • P17 0-10v enabled = 0

Important: remove the aluminum bus bars from relays 5–8 for this configuration.

Connecting variable speed fans

0-10v VFDs can be connected and their speed controlled automatically by temperature. VFDs use 2 signals, a speed signal and a start signal. Wiring consists of both these signals which always takes at least 4 conductors.

The speed signal is dc voltage which varies between 0-10v volts. 10v is 100% speed, 0 = stopped (but still energized). The start signal is a Normally Open switch to tell the VFD when to energize the motor.

Wiring diagram for a 0-10v VFD-driven fan on the CAPTAIN 10 showing the 0-10v positive and negative speed signal, the blue and white start-signal conductors, and 24vdc curtain motors on relays 1 to 6, with an inset photo of the VFD terminal block
A 0-10v variable-speed fan: a 0-10v speed signal plus a separate Normally Open start signal. The inset photo shows the VFD terminal block.

Configuration needed to match this diagram:

  • P0 Number of curtains = 3
  • P1 Curtain starting relay = 1
  • P2 Number of fans = 1
  • P3 Fan starting relay = 9
  • P4 Number of heaters = 0
  • P6 Number of lights = 0
  • P8 Number of soakers = 0
  • P17 0-10v enabled = 1

Important: remove the aluminum bus bars from relays 7 & 8 for this configuration.

Multiple VFDs can be connected in series. The maximum varies by brand. The limit varies between 5 and 50 VFDs. AutoVent brand VFDs have a max of 50.

Reconfigurable outputs

Fans, heaters, lights, and curtain motors can be mapped to any relay. The only limitation is that multiples of an equipment type use consecutive relays.

Example: if there are 4 fans (as per parameter P2) and the fan’s start relay is 1 (parameter P3), relays 1 thru 4 will be the fan circuits.

Screen overview & overrides

The screen shows you what is happening. You can see the temperature and the status of the relays. Press on the temperature to go to your settings. Press the bottom row of buttons to manually override.

CAPTAIN touch screen showing the time 1:41, No Rain, a temperature of -35 degrees and 0.0 MPH, with Auto buttons for Vent1 to Vent4 open and close plus Fan1 and Fan2, and the Vent3 close button highlighted green
The status screen shows temperature, wind, rain status, and the manual override buttons for each output.
CAPTAIN override screen for Output 2 Fan #-2 showing three buttons: auto highlighted green, off, and forced on
Select the relay status you want. In Auto it operates automatically; Off or Forced lets you avoid the control system. To exit, press the blank space on the sides.

Parameter reference

There are parameters that you can change. The parameters are labeled P1, P2… These parameters are the temperature setpoints and values you can adjust. From the parameter screen you can scroll to other parameters and edit each parameter ID.

CAPTAIN parameter editing screen showing Prior and Next scroll buttons, Parameter ID P31, a value of 65 with minus and plus buttons, the label summer start degrees, and Exit menu and Save buttons
The parameter editing screen: scroll between parameters with Prior/Next, adjust the value, then Save.

Curtain parameters

Curtain parameters
IDDescriptionDefaultMinMax
P101–P103Open temperature for Curtains #1 – Curtain #10.60°1°99°
P131–P133Curtain #1 – Curtain #3’s run seconds. How many seconds the curtain runs per interval.15  
P141–P143Curtain #1 – Curtain #3 pause minutes. The time the curtain waits between intervals.50  
P151–P153Curtain #1 – Curtain #3 ventilation temperature gap. The difference between open and shut temperature.50  
P170Curtain motor’s max humidity. Humidity at which the curtain will open to dry things.95  
P171Seconds the curtain will open for the humidity event.10  
P172Humidity limits temperature. Humidity will be disregarded if it’s too cold.32  
P181–P190Curtain #1 – Curtain #10 sequence. If vent should wait on another curtain to close first from rain or high wind.0  
P191–P200Curtain #1 – Curtain #10 how long it takes a curtain to shut. Closing seconds for rain or high wind events.100  
P201High wind curtains – which curtains should shut from wind.0  
P202High wind MPH – wind event on.53  
P203Wind override clear MPH – wind event off.50  
P204If the curtains should open quickly after wind event goes off (P191 = rains seconds). 0 = no, 1 = yes.0  

Fan temperature parameters

The temperature parameters control the starting temperature. The fans are used for cooling. They will turn on above the temperature setpoint. If humidity is connected, fan #1 can be set to clear out the high humidity.

Fan temperature parameters
IDDescriptionDefaultMinMax
P301–P306Start temperature for Fan #1 – Fan #6.0°1°99°
P331Fan temperature gap. Difference between on and off.0.3  
P341Fan max MPH. If wind sensor is connected, MPH at which fans will stop.0  
P342MPH deadspan.0  
P350Fan #1 max humidity. If humidity sensor is installed, when fan #1 will start to dry out the building (set to 101% to disable humidity function).99%RH  
P351Fan humidity hysteresis – 5%.101  
P352Fan humidity low-temperature limit.32°  
P361–P366Fan #1 – Fan #6’s high-temperature limit.0  

THI index

The THI index uses the average temperature and the humidity to turn the fans on sooner. This allows the controller to think more like a cow. You can adjust how much humidity and high temperatures affect the index.

CAPTAIN THI index screen showing an effective temperature of 73.8 degrees, an 8-hour average of 66.7 degrees, 0 percent RH is adding 0.0 degrees, and a 75 degree average will add 6 degrees
The THI index screen: effective temperature, the rolling 8-hour average, and how much humidity and high temperatures add to the effective temperature.
THI index parameters
IDDescriptionDefaultMinMax
P391If THI index should be enabled. 0 = no, 1 = temperature based only, 2 = humidity and temperature based THI.002
P392Hot temperature trigger, i.e. how high is the average temperature to be considered hot?75°1°99°
P393How many degrees are added to the effective temperature when it’s hot.6°1°20°
P394How many hours are included in the rolling temperature average.8124
P395Optional – when humidity starts affecting the effective temperature.60%RH10%95%
P396At 99% humidity – how much the index is influenced by humidity. By default, 6 degrees will be added to the THI index when it’s 99%RH. This influence scales down as the humidity drops. It will have zero at P395 humidity.6°020

Variable fan parameters

Controlling the speed signal: the variable speed output is a 0-10v signal. This means the controller outputs 10v to indicate 100% speed to a VFD, 0v to indicate no speed. The VFD will run at the minimum speed when the temperature reaches the “start temperature.” As the temperature continues to rise the VFD will run faster until it reaches 100% speed. The VFD is at 100% speed when the temperature reaches “Max speed.”

You can add 2 additional 0-10v zones with a KVT-EX02 expansion module. P17 sets the number of zones you wish to use.

CAPTAIN variable-speed fan screen showing 16 percent speed, 65 degrees start at 16 percent speed, 80 degrees is full speed, and a note that speed changes automatically by temperature
The variable-speed fan screen: the low-speed start temperature, the current speed, and the full-speed temperature.
CAPTAIN status screen showing the time 16:56, 75.6 degrees, 0.0 MPH, a barn temperature of 69.0 degrees and 26 percent RH, with Fan #1 and Fan #3 highlighted green as running and Fan #2 off
A status screen showing barn temperature, humidity, and which fans are running (green).
Variable fan parameters
IDDescriptionDefaultMinMax
P401Low-speed temperature for variable fans.50°1°99°
P402High-speed temperature for variable fans.85°  
P403Low speed for variable fans.20%  
P404Manual speed for variable fans. 11 = Automatic, 10 = Forever at 100%, 5 = Forever at 50%, 1 = Forever at 10%.11111
P405Fan speed if humidity is high.98  
P410Optional Zone 2 low-speed temperature for variable fans.50°1°99°
P411Optional Zone 2 high-speed temperature for variable fans.85°  
P412Optional Zone 2 low speed for variable fans.20  
P413Optional Zone 2 manual speed for variable fans.11199°
P405Optional Zone 2 fan speed if humidity is high.98  
P420Optional Zone 3 low-speed temperature for variable fans.50°1°99°
P421Optional Zone 3 high-speed temperature for variable fans.85°  
P422Optional Zone 3 low speed for variable fans.20  
P423Optional Zone 3 manual speed for variable fans.11199°
P425Optional Zone 3 fan speed if humidity is high.98  
P429Variable speed off mode. When temperature is below P401 the speed signal will be: 0 = minimum speed /P403, 1 = off.001

Milking time

If you want the fans and soakers to only be on certain times of the day, the milking schedule is for you. Enable P40 and then fans and soakers will only run if it’s during a milking time.

Milking time
IDDescriptionDefaultMinMax
P550Milking time on – 1st milking.0.000:0424:00
P551End of 1st milking time.0.000:0424:00
P552Milking time on – 2nd milking.0.000:0424:00
P553End of 2nd milking time.0.000:0424:00
P554Milking time on – 3rd milking.0.000:0424:00
P525End of 3rd milking time.0.000:0424:00

P40 must be enabled for milking times to be enabled on the unit.

Light timer

The lights are a simple time clock that goes on and off based on the time you enter. It is based on 24hr time in 6-minute intervals.

Light timer
IDDescriptionDefaultMinMax
P560Time on for lights. Period A.0.000:0424:00
P561Time off for lights. Period A.0.000:0424:00
P562Time on for lights. Period B.0.000:0424:00
P563Time off for lights. Period B.0.000:0424:00

Heater parameters

The parameters control the starting temperature.

Heater parameters
IDDescriptionDefaultMinMax
P601–P610Heater 1 – Heater 10’s setpoint°.60°1°100°
P631Heater hysteresis.2.0°  

Evaporative cooling

The evaporative cooling app is for running high pressure misting or cool cells. It has 1 or 2 stages. High pressure misting with a pump and lots of nozzles potentially would use both stages.

As it gets more humid, the evaporative cooling can automatically turn off to keep the barn from becoming saturated. If the system cycles too quickly, increase the hysteresis and time delay between stages.

Evaporative cooling parameters
IDDescriptionDefaultMinMax
P580Stage 1 start temperature. How warm it needs to be for the system to start.75°  
P581Stage 2 start temperature. How warm it needs to be for more cooling to be engaged.85°  
P582Max humidity / RH% for stage 1 to operate, i.e. if it gets muggier than this it will not start.75%  
P583Max humidity / RH% for 2nd stage to operate, i.e. if it gets muggier than this it will not allow the 2nd stage to operate.82%  
P584Temperature hysteresis or difference between on and off. Adjust this to prevent excessive cycling from temperature swings.2.0°  
P585Humidity hysteresis or difference between on and off due to humidity.2.0  
P586Stage time delay. Minimum minutes between stage 1 and 2.5.0  
Evaporative cooling configuration
IDDescriptionDefaultMinMax
P14Number of stages in system.0 2
P15Starting relay for the evaporative cooling, i.e. which output relay stage 1 will be. Stage 2 will be the next relay (if enabled). A cool cell pad system would most likely just use 1 zone.1  

Duty cycle fan

The duty cycle fan was intended to control a fan to provide a variable amount of air by stopping and starting it. You can set how long the cycle is to keep it from cycling too often. Cycling too often will prematurely wear the contacts and your motors.

Note: to keep it from short cycling, above 95% the fan will be on regardless.
Duty cycle fan parameters
IDDescriptionDefaultMinMax
P850Start temperature. However, a 0 means it’s on always to maintain minimum ventilation.40°1°100°
P851Begin accelerating temperature.60°1°100°
P852Always on temperature. The duty cycle is at 100% and the fan will not turn off.801120°
P853Minimum %. The least amount the duty cycle fan will be on.10%5%100%
P854Cycle minutes. How long an on/off cycle will be.3120

Soakers

The soakers function by turning a valve on and off. The spray and dry-off times ramp between setpoints to give you an infinitely adjusted water output. For reduced water demand, each zone takes turns spraying. It controls up to 6 individual soakers. The amount of water used and how often it sprays is controlled by the temperature or temperature index.

Sprinkler temperature settings

The spray time ramps between low and high spray seconds with the barn temperature. The first zone has its own spray seconds. The remaining zones share spray settings.

The dry-off / interval time ramps between low and high dry-off minutes with the barn temperature. All zones share the dry-off minutes. The interval time is the amount of time each zone waits between sprinkles.

In the eastern USA, it’s typical to spray for about 30–60 seconds. This varies with the spray tip size. The goal is to get the cow wet but not running onto her udder. When the side of the leg is wet, it’s time to stop. The dry-off time usually is 15 minutes at 70° and 5 minutes at 90°.

Application note: a 100 lb cow, laying in a freestall, will overheat within 90 minutes at 5 MPH @ 90° @ 70%RH. Getting a cow’s body temperature down from 102° to 100° takes 5 cycles. This means a theoretical 25 minutes at 90°. If the cow is drying off before 5 minutes in very hot weather, a 3-minute high dry-off time gets her cooled down in 15 minutes.
Soaker parameters
IDDescriptionDefaultMinMax
P800Soaker start temperature.75°1°99°
P801Soaker high temperature.95°1°99°
P802Soaker dry-off minutes when the temperature is at the start temperature.15125
P803Soaker dry-off minutes when the temperature is at the high temperature.5125
P804Spray seconds at low for zone #1.301250
P805Spray seconds at high for zone #1.301250
P806Spray seconds at low for zone #2–6.301250
P807Spray seconds at high for zone #2–6.301250

Setup configurations

Setup configuration parameters
IDDescriptionDefaultMinMax
P0Number of curtains.203
P1Curtain starting relay.101
P2Number of fans in the system.106
P3Fan starting relay.506
P4Number of heaters.2 6
P5Heater starting relay.8 6
P6Number of grow lights.011
P7Grow lights starting relay.1 6
P8Number of sprinkler circuits.006
P9Starting relay for the sprinklers.116
P12Duty cycle fan enabled. 0 = no, 1 = yes.0 1
P13Duty cycle fan relay.0 6
P14Evaporative cooling app enabled. 1 = single stage, 2 = dual stage.002
P15Evaporative cooling relay for stage.   
P16If 0-10v zone 1 should use humidity instead of temperature. 0 = No, 1 = Yes.001
P17Number of 0-10v zones in system.013
P180-10v low-temperature volts. Normally this is zero unless you want 10v to shut the fan off.0010
P190-10v high-temperature volts. Volts at high temperature.10010
P20Is 2nd temperature sensor enabled.0  
P21Is humidity sensor enabled.0  
P22Temperature probe 1 offset.0.0-10.0+10.0
P24Fahrenheit or Celsius.F  
P27Wind response time minutes.3  
P28Anemometer calibration.252 
P29Windmeter enabled.0  
P30Revert controller to defaults.315
P39Milking timeclock enable, i.e. do you want fans and soakers to only be enabled for select periods during the day. 0 = no, 1 = yes.0 1
P40When raining, max curtains allowed to close simultaneously. Too many can trip the 24v curtain breaker.1110
P41–P49Curtain #1 – Curtain #3 rain sensor uses input #. You select which input a curtain’s rain sensor is connected to.0  
P60Fan high-temperature shutoff enabled? 0 = no, 1 = yes.   
P61–P70Turn fan 1 – fan 10 input off.0  
P71How many curtains use 2nd temperature sensor.0  
P72How many heaters use 2nd temperature sensor.0  
P73How many fans use 2nd temperature sensor.0  

Specifications

CAPTAIN 10 (AV10PS) dairy specifications
Size of enclosure7″ × 10″ × 6″
Input voltage120VAC
Output10 Normally open relays
Temperature sensorThe 3-foot cord can be extended to 100 ft.
Warranty1 year