Troubleshooting KVT-400

Screen blinks on and off without showing any error codes


Only showing the autovent logo with a black background briefly, then going black.


Several seconds later it does it again.

The wind sensor gets power from the controller/ screen board. If the wind sensor shorts out, the controller and screen will restart.

Test 1.

Take a picture so you know how to reconnect the wires

Disconnect terminal 96
Disconnect rain sensor’s 3rd terminal Labeled blue.

Does controller still reboot:

Stopped rebooting: Go to Test 2

Still reboots : Disconnect all terminals. 96,97,98,& 99 and all 4 rain sensor terminals.

If it still reboots, check power supply voltage. Should be 24vdc between terminals 30&31. Should be 3.3v between 96&97.

Test 2. Testing wind sensor wires

Testing wind sensor wires

This test assumes the controller stopped rebooting
when the all weather sensor wires where disconnected
in test 1.
Go up to weather sensor junction box:
– Take picture of wires inside the junction box.

– Disconnect all of the 8 wires coming up from the
controller.
Make sure none of the now loose wires are touching
each other
– Reconnect all the wires down at the controller.
Does the controller reboot with only the wire connected?
No- Replace wind sensor – or Disconnect wind and then rains sensor to a certain issue is with wind
sensor ( most likely)
Yes- Replace wire

Expansion box 6th relay from right on forever.
Livestock Comfort
Remote Management

Specs

Managed Equipment

  • Curtains & Baffles
  • Circulation & Tunnel Fans
  • Feedline Soakers
  • Barn Lighting

Standard Sensors

  • Temperature Sensor
  • Rain & Wind Speed
  • Wind Direction
  • Optional: Humidity/Ammonia

Technical Specs

  • (10) 7.5 AMP SPDT Outputs
  • (1) 0-10v Variable Speed Output
  • 120/240V Input Power
  • Built-in Wiring Aids
Category KVT-400 Base Unit With Expansion Options
Primary Outputs (10) 7.5 AMP SPDT Relays Up to 26 total relays
Variable Speed (1) 0-10v (up to 20 drives) +2 additional 0-10v banks
Sensor Suite Temp, Rain, Wind Speed/Direction Optional: Humidity or Ammonia
Connectivity Local Wi-Fi Gateway AT&T Cellular Service
Power Input 120/240 VAC Built-in wiring aids
Pro Tip: For DC motor setups, the KVT-400PS version is "Plug & Play"—just connect the power and motor leads.

Why AutoVent?

AutoVent was founded by Kevin Hoover out of a simple necessity: Most controllers didn’t know how to handle wind.

 

While other systems blindly close every curtain when the temperature drops, the KVT-400 is built to be selective. By closing only the windward side, your barn maintains maximum air exchange at lower temperatures, keeping your herd dry and respiratory-risk-free.

Ready to Automate Your Barn?